What battery bank capacity does a two-day autonomy need?

  • Design Challenge
  • Renewable Energy
  • intermediate
Competency Design and sizing primary Systems and balances supporting Quantitative reasoning supporting

What you should take away: Size battery bank energy and amp-hour capacity from daily load, autonomy and depth of discharge, before arranging series and parallel strings.

The situation

What is happening

An off-grid load uses 4.8 kWh/day. The battery bank must provide two days of autonomy at a 48 V system voltage and an 80 % depth of discharge. The selected batteries are 100 Ah at 12 V. What bank capacity in amp-hours is required?

Given

Scenario values with units
QuantityValueUnitNote
Daily energy 4.8 kWh/day Load energy per day.
Autonomy 2 days Days without solar input.
System voltage 48 V Nominal DC bus.
Depth of discharge 80 % Maximum usable fraction.
Battery rating 100 Ah Each battery is 12 V, 100 Ah.

Assumptions this challenge makes

  • The load is constant at 4.8 kWh/day.
  • The depth-of-discharge limit is applied to the nameplate bank energy.
  • Battery ageing, temperature and inverter efficiency are not included.

Your call

Your answer

Enter the bank capacity at the 48 V system voltage, before choosing series and parallel strings.

What this challenge does not establish

  • The load is treated as constant; a real load profile and inverter efficiency change the required energy.
  • Temperature, ageing and Peukert losses are not modelled.
  • The depth of discharge is a stated limit, not a property of every battery technology.
  • The result does not size the array, charge controller, inverter or protective devices.